OPTO 22 – GRV-OVMALC-8 _ Analog output, 8 channels, voltage or current, chassis-powered loop
Quick Specs:
- Analog output
- 8 channels
- voltage or current
- chassis-powered loop
The GRV-OVMALC-8 analog output module has 8 channels, individually configurable for any one of seven voltage or current output ranges:
- 0 to 5 VDC
- 0 to 10 VDC
- -5 to +5 VDC
- -10 to +10 VDC
- 0 to 22 mA
- 4 to 20 mA
- 0 to 20 mA
Each range has 4096 counts (12 bits) of resolution. See the Specifications tab for more information.
For current outputs, the GRV-OVMALC-8 also provides an isolated loop supply.
Part of thegroovEPIC® system, the GRV-OVMALC-8 mounts on agroovEPIC chassis with a GRV-EPIC-PR1 processor and other analog, discrete, and serialgroovI/O modules, to give you the mix of signals you need.
Specifications:
| Features | GRV-OVMALC-8 |
| Channel-to-Channel Isolation | |
| Watchdog Timeout Value | x |
| Scaling | x |
| Ramping | x |
| Clamping | x |
| Problem indication | x |
| Specification | GRV-OVMALC-8 |
| Output Ranges (Resolution) | Voltage
0to5VDC (1.22 mV)0to10 VDC (2.44 mV) -5to +5VDC (2.44 mV) -10 to +10 VDC (4.88 mV) Current 0 to 22 mA (6 microamps) 4 to 20 mA (4 microamps) 0 to 20 mA (5 microamps) |
| Resolution | Range / 4096 (12-bits) |
| Accuracy | ± 0.1% of span |
| Max Current for Voltage Output | 10 mA |
| Output impedance | 280 Ohms |
| External current loop power | N/A, internal loop power only |
| Maximum current loop resistance | 750 Ohms |
| Data Refresh Time | 10 ms |
| Problem Indication | Current outputs: Open circuit / Voltage outputs: Over-current |
| Isolation (field-to-logic) | 300 V working, 1500 V transient (1 minute) |
| Isolation (channel-to-channel) | None |
| Number of Channels | 8 |
| Chassis Power Consumption | 1.8 W all voltage outputs / 6.2 W all current outputs |
| Minimum GRV-EPIC-PR1 Firmware Version | 1.0.0 |
| Minimum PAC Project Version | 10.000 |
| Wire Size | 28 – 14 AWG |
| Torque, connector screw | 2.5 in-lb (0.28 N-m) |
| Torque, hold-down screw | 3.5 in-lb (0.4 N-m) |
| Temperature (operating) | -20 °C to +70 °C |
| Temperature (storage) | -40 °C to +85 °C |
| Relative Humidity (non-condensing) | 5 – 95% |
| Agency Approvals | UL/cUL (Class 1 Div. 2)a; CE, ATEX (Category 3, Zone 2), RoHS; DFARS; CB Scheme; UKCA |
| Warranty | Lifetime |
| a For use in hazardous locations, equipment must be mounted in an enclosure that meets the requirements of the National Electrical Code, ANSI/NFPA 70, and ANSI/ISA-61010-1 (82.02.01). |